ABB i-bus
®
KNX
Parameters
326 2CDC508198D0211 Rev. A | AC/S 1.x.1
Object name
Object type
Unit
COV send
condition
Heat generator: Max. room setpoint temperature
Analog value
°C (62)
1.0
This module has this BACnet output object if the Yes option is selected for the Supply temperature control parameter, the
Calculated weather compensated option is selected for the Supply setpoint temperature source parameter and the Based on
the current room setpoint temperatures option is selected for the Economy mode parameter.
Outputs the highest room setpoint temperature that is present on the ASM input socket and that is used by the Economy mode
function.
Signal value: -273...670760 °C
Heat generator: Heat generator On/Off
Binary value
-
-
The module has this BACnet output object in the following conditions:
• If the Yes option is selected for the Supply temperature control parameter and the Yes option is selected for the
Enable
heat generator based on ASM input socket parameter.
• If the Yes option is selected for the Switch off if no room demand
parameter.
Outputs the on/off status of the heat generator that is sent to the heat generator via the related group object. The state is
dependent on the Enable heat generator based on ASM input socket and Switch off if no room demand functions as well as
override via the web user interface.
Signal value: 0 = Off
1 = On
Heat generator: Room involvement Analog value °C (62) 1.0
The module has this BACnet output object if the
Yes
option is selected for the
Supply temperature control
parameter, the
Calculated weather compensated option is selected for the Supply setpoint temperature source parameter and the Yes option
is selected for the Room involvement parameter.
Outputs of current value by which the supply setpoint temperature is increased or reduced by the Room involvement function.
Signal value: -273...670760 °C

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB i-bus KNX AC/S 1.x.1 Series and is the answer not in the manual?

ABB i-bus KNX AC/S 1.x.1 Series Specifications

General IconGeneral
BrandABB
Modeli-bus KNX AC/S 1.x.1 Series
CategoryController
LanguageEnglish

Related product manuals