ABB i-bus
®
KNX
Parameters
AC/S 1.x.1 | 2CDC508198D0211 Rev. A 391
Object function
Name (can be changed separately)
Data type
Flags
Output: Chiller On/Off Chiller 1 bit
DPT 1.001
C, R, T
The module has this group object in the following conditions:
If the Yes option is selected for the Supply temperature control parameter and the Yes option is selected for the
Enable
chiller based on ASM input socket parameter.
If the Yes option is selected for the Switch off if no room demand
parameter.
The chiller is switched on/off via this group object based on the calculations in the module.
Telegram value:
0 = Off
1 = On
Input: Chiller operating status
Chiller
1 bit
DPT 1.011
C, W, T
The module has this group object if the Yes option is selected for the Show operating status parameter.
Input for the operating status (Off/On) provided by the chiller. Due to the control integrated into the chiller, this status may
differ from the operating status specified by this module.
Telegram value:
0 = Inactive
1 = Active
Input: Chiller fault status
Chiller
1 bit
DPT 1.011
C, W, T
The module has this group object if the Yes option is selected for the Show fault status parameter.
Input for the fault status provided by the chiller.
Signal value: 0 = Inactive
1 = Active