Parameters
390 2CDC508198D0211 Rev. A | AC/S 1.x.1
Object function
Name (can be changed separately)
Data type
Flags
Input: Pump fault Chiller 1 bit
DPT 1.011
C, W, T
The module has this group object if the Yes option is selected for the Pump display pump fault status parameter.
The fault state of the pump can be received via this group object and evaluated by the device
Telegram value: 0 = Inactive
1 = Active
Input: Pump operating status (Off/On)
Chiller
1 bit
DPT 1.011
C, W, T
The module has this group object if the Yes option is selected for the Pump display operating status parameter.
Input for the operating status (Off/On) provided by the pump. On pumps with their own control, this operating status can differ
from the operating status of the chiller.
Telegram value: 0 = Inactive
1 = Active
In-/Output: Pump override disable/enable Chiller 1 bit
DPT 1.003
C, R, W, T
The module has this group object if the
Yes
option is selected for the
Override by WebUI
parameter.
This object activates/deactivates the pump override for the chiller.
Telegram value:
0 = Disabled
1 = Enabled
In-/Output: Pump override value
Chiller
1 bit
DPT 1.001
C, R, W, T
The module has this group object
if the Yes option is selected for the Override by WebUI parameter.
This object specifies the state with which the pump for the chiller is overridden if the pump override is active.
Telegram value: 0 = Off
1 = On