ABB i-bus
®
KNX
Parameters
90 2CDC508198D0211 Rev. A | AC/S 1.x.1
Greater Than (GREATER)
Comparison of two input values. Both inputs can also be linked with fixed values (constant).
Inputs
No.
DPT
Abbr.
Name
Visible
Description
1
Numerical value
I
1
Input value
Always
2
Same as input 1
I
2
Input value
Parametrizable
Outputs
No.
DPT
Abbr.
Name
Visible
Description
1
1 bit
A
Output
Always
Parameters
Name
Value
Visible
Description
In 2
Checkbox
Always
Numerical value
If the checkbox is
cleared
Data type as for input 1
Function
The output is 1 if I
1
is greater than I
2
.
The output is 0 if I
1
is less than or equal to I
2
.
Whenever a telegram is received the output starts a recalculation independently if the value has changed.