Section 8 Establishing connection and verifying the
SPA/IEC communication
8.1 Entering settings
M11735-2 v2
If the IED is connected to a monitoring or control system via the rear SPA/IEC103
port, the SPA/IEC103 port has to be set either for SPA or IEC103 use.
8.1.1 Entering SPA settings
M11735-7 v5
The SPA/IEC port is located on the rear side of the IED. Two types of interfaces can be
used:
plastic fibres with connector type HFBR
glass fibres with connector type ST
When using the SPA protocol, the rear SPA/IEC port must be set for SPA use.
Procedure:
1. Set the port for SPA use on the local HMI under Main menu /Configuration /
Communication /Station communication/Port configuration/SLM optical
serial port/PROTOCOL:1. When the communication protocol is selected, the
IED is automatically restarted, and the port then operates as a SPA port.
2. Set the SlaveAddress and BaudRate for the rear SPA port on the local HMI under
Main menu/Configuration/Communication/Station communication/SPA/
SPA:1. Use the same settings for these as is set in the SMS system for the IED.
8.1.2 Entering IEC settings
M11735-32 v5
The SPA/IEC port is located on the rear side of the IED. Two types of interfaces can be
used:
plastic fibres with connector type HFBR
glass fibres with connector type ST
When using the IEC protocol, the rear SPA/IEC port must be set for IEC use.
1MRK 502 073-UUS A Section 8
Establishing connection and verifying the SPA/IEC communication
Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062 97
Commissioning manual