ABB REG670 - Test of the Point SE

ABB REG670
324 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
frequency of V
ts
= 50 Hz
I I
I
I
A
s
CTs
CTp
50 50
10459
1
9000
1 162= × = × = .
EQUATION14059 V1 EN-US (Equation 55)
I
50s
= 0º
frequency of I
50s
= 50 Hz
It I
I
I
A
fs
CTs
CTp
tf= × = × =10459
1
9000
1 162.
EQUATION14062 V1 EN-US (Equation 56)
I
tfs
= 180º
frequency of I
tfs
= 49.5 Hz
Expected result: start of the protection function and trip in zone 1 when trip
conditions are fulfilled.
13.4.5.4 Test of the point SE (R
RvsR
, X
RvsX
)
GUID-335F54E6-52DE-4BF1-A34B-0C2DB8059CC1 v1
The trajectory of the impedance traverses the lens characteristic in zone
1
GUID-2DD20D2E-6188-4631-A584-5E68B212E011 v1
Preliminary steady state test at 50 Hz
GUID-7BCF3D7B-1B84-46D4-B9E3-066894A878E8 v1
Go to Main menu/Test/Function status/Impedance protection/
OutOfStep(78,Ucos)/OOSPPAM(78,Ucos):1/Outputs to check the available
service values of the function block OOSPPAM.
Apply the following three-phase symmetrical quantities (the phase angle is related
to phase L1):
V V
V
V
V
ts t RvsZ
VT s
VT p
= × × = × × =0 9 0 9 5899
0 1
13 8
38 47. .
.
.
.
,
,
,
EQUATION14067 V1 EN-US (Equation 57)
29.60
arctan 180 arctan 180 90.56
0.29
ts
ReverseX
V
ReverseR
Ð = - ° = - ° = - °
æ ö æ ö
ç ÷ ç ÷
è ø è ø
EQUATION14068 V1 EN-US (Equation 58)
frequency of V
ts
= 50 Hz
I I
I
I
A
s
CTs
CTp
50 50
10459
1
9000
1 162= × = × = .
EQUATION14059 V1 EN-US (Equation 59)
Section 13 1MRK 502 073-UUS A
Testing functionality by secondary injection
174 Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062
Commissioning manual