12.8.2.1 Enable forcing by using LHMI
GUID-41F7C636-75BC-42EF-A955-4BD9E347619E v2
1. Enable IED TESTMODE by setting IEDTestMode to On under Main menu/
Test/IED test mode/TESTMODE:1.
IEC15000029 V1 EN-US
2. Exit back to the root menu.
3. Select Yes in the save dialogue box.
Once the IED is in test mode the yellow Start LED starts to blink.
12.8.2.2 Enable forcing using TESTMODE function block
GUID-DD17B7D6-516F-4561-9D30-906B968EAFE0 v1
• Use the TESTMODE function block, appropriately configured in PCM600/ACT.
It may be convenient to control the input on mentioned component from, for example,
an LHMI function key or similar during commissioning to quickly and easily enter
IED test mode.
12.8.3 How to change binary input/output signals using forcing
GUID-7DF9FAF1-68B1-49AF-9DE4-2A8D6F6FAEFE v1
Once the IED is in IED test mode, the LHMI/PCM600 menus can be used to control
input/output signals freely.
1MRK 502 073-UUS A Section 12
Testing IED operation
Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062 131
Commissioning manual