EasyManua.ls Logo

ABB REG670 - Measuring the Trip Value for the Zero-Sequence Function

ABB REG670
324 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2
2
3
A B C
V V a V a V× = + × + ×
EQUATION1818-ANSI V1 EN-US (Equation 107)
Where:
A B C
andV V V
EQUATION1820-ANSI V1 EN-US
are the measured phase voltages
2
3
3
1 0,5
2
j
a e j
p
×
= × = - +
.
IECEQUATION00022 V2 EN-US
4. Compare the result with the set value of the negative-sequence operating voltage
(consider that the set value 3V2PU is in percentage of the base voltage VBase).
5. Repeat steps 1 and 2. Then slowly increase the measured current in one phase
until the BLKV signal disappears.
6. Record the measured current and calculate the corresponding negative-sequence
current according to the equation (observe that the currents in the equation are
phasors):
2
2
3
A B C
I I a I a I× = + × + ×
ANSIEQUATION00021 V1 EN-US (Equation 108)
Where:
A B C
I I and I ,
ANSIEQUATION00020 V1 EN-US
are the measured phase currents
2
3
3
1 0,5
2
j
a e j
p
×
= × = - +
.
IECEQUATION00022 V2 EN-US
7. Compare the result with the set value of the negative-sequence operating current.
Consider that the set value 3I2< is in percentage of the base current IBase.
13.9.2.3 Measuring the trip value for the zero-sequence function
M1405-72 v11
Measure the trip value for the zero-sequence function, if included in the IED.
1MRK 502 073-UUS A Section 13
Testing functionality by secondary injection
Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062 243
Commissioning manual

Table of Contents

Other manuals for ABB REG670

Related product manuals