Table 15: LON node information parameters
Parameter Range Default Unit Parameter description
NeuronID* 0 - 12 Not loaded - Neuron hardware identification number in
hexadecimal code
Location 0 - 6 No value - Location of the node
*Can be viewed on the local HMI
ADE settings are available on the local HMI under Main menu/Configuration/
Communication/Station communicaton/LON/ADE:1
Table 16: ADE Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Disabled
Enabled
- - Disabled Operation
TimerClass Slow
Normal
Fast
-
- Slow Timer class
LON commands are available on the local HMI under Main menu/Configuration/
Communication/Station communication/Port configuration/SLM optical LON
pot/Service Pin Messae/Generate service pin message
Table 17: LON commands
Command
Command description
ServPinMess Command with confirmation. Transfers the node address to the LON Network Tool.
9.2 Optical budget calculation for serial communication
with LON
M11737-4 v2
Table 18: Example
Distance 1 km
Glass
Distance10 m
Plastic
Maximum attenuation -11 dB - 7 dB
4 dB/km multi mode: 820 nm - 62.5/125 um 4 dB -
0.3 dB/m plastic: 620 nm - 1mm - 3 dB
Margins for installation, aging, and so on 5 dB 2 dB
Losses in connection box, two contacts (0.75 dB/contact) 1.5 dB -
Table continues on next page
Section 9 1MRK 502 073-UUS A
Establishing connection and verifying the LON communication
104 Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062
Commissioning manual