13.11.1.4 Completing the test
SEMOD54375-203 v6
Continue to test another function or end the test by changing the TESTMODE setting to
Disabled. Restore connections and settings to their original values, if they were
changed for testing purposes.
13.11.2 Integrator TIGAPC
GUID-D18B2BCA-A79B-4B04-860C-BE2122FECEA7 v2
The integrator function TIGAPC can be tested by connecting a binary signal to the
input of the function and applying pulses to the function. Normally the Integrator will
be tested when testing the function the integrator is connected to, such as reverse
power, loss of excitation and pole slip. When the function is configured, test it together
with the function that operates it.
13.11.2.1 Completing the test
GUID-5CD0314D-7D02-477E-BC16-12C82534E72D v2
Continue to test another function or end the test by changing the Test mode setting to
Disabled. Restore connections and settings to their original values, if they were
changed for testing purposes.
13.12 Monitoring
SEMOD53581-1 v1
13.12.1 Gas medium supervision SSIMG
GUID-0A83B4D5-51FF-43CB-8DC7-AFCEA2BC7B69 v2
Prepare the IED for verification of settings as outlined in Section
"Preparing the IED to
verify settings" in this chapter.
Values of logical signals for SSIMG protection are available on the local HMI under
Main menu/Tests/Function status/Monitoring/InsulationGas(63)/SSIMG(63):x,
where x = 1, 2,....21.
The Signal Monitoring in PCM600 shows the same signals that are available on the
local HMI.
Check that the input logical signal BLOCK is logical zero and that on the local HMI,
the logical signals PRESALM, PRESLO, TEMPALM, TEMPLO, ALARM and LOCKOUT
are logical zero.
Section 13 1MRK 502 073-UUS A
Testing functionality by secondary injection
272 Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062
Commissioning manual