50s
= 0º
frequency of I
50s
= 50 Hz
It I
I
I
A
fs
CTs
CTp
tf= × = × =10459
1
9000
1 162.
EQUATION14062 V1 EN-US (Equation 60)
I
tfs
= 0º
frequency of I
tf
= 50 Hz
Check that the service values (VOLTAGE, CURRENT, R(%), X(%)) are
according to the injected quantities and that ROTORANG is close to 3.14 rad. For
this particular injection the service values are:
VOLTAGE = 5.31 kV
CURRENT = 20918 A
R = -0.26%
X = -26.65%
ROTORANG = -3.06 rad
Note that these values identify a point inside the lens characteristic in zone 1 that
is close to the point SE. The START is issued, but no TRIP is performed.
Execution of the dynamic test
GUID-FF6DCD5B-96AA-4255-8740-B85C8C7148F5 v1
The test may be performed by using two states of a sequence tool that is a basic feature
of test sets.
State 1: pre-test condition.
Steady voltage and current are applied in order to get a steady high impedance,
that is a point in the plane R-X which is far away from the lens characteristic.
Define the following three-phase symmetrical quantities (the phase angle is related
to phase L1):
V V
V
V
V
ts t RvsZ
VT s
VT p
= × × = × × =0 9 0 9 5899
0 1
13 8
38 47. .
.
.
.
,
,
,
EQUATION14067 V1 EN-US (Equation 61)
29.60
arctan 180 arctan 180 90.56
0.29
ts
ReverseX
V
ReverseR
Ð = - ° = - ° = - °
æ ö æ ö
ç ÷ ç ÷
è ø è ø
EQUATION14068 V1 EN-US (Equation 62)
frequency of V
ts
= 50 Hz
I
50s
= 0 A
I
tfs
= 0 A
State 2: main test step.
1MRK 502 073-UUS A Section 13
Testing functionality by secondary injection
Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062 175
Commissioning manual