Check that the service values (VOLTAGE, CURRENT, R(%), X(%) ) are
according to the injected quantities and that ROTORANG is close to 3.14 rad. For
this particular injection the service values are:
VOLTAGE = 10.74 kV
CURRENT = 20918 A
R = 7.37%
X = 53.40%
ROTORANG = -3.09 rad
Note that these values identify a point inside the lens characteristic, in the zone 2,
that is close to the point RE. The START is issued, but no TRIP is performed.
Execution of the dynamic test
GUID-028D7D67-B61A-4A7F-9978-4A0A41231B04 v1
The test may be performed by using two states of a sequence tool that is a basic feature
of test sets.
State 1: pre-test condition.
Steady voltage and current are applied in order to get a steady high impedance,
that is, a point in the plane R-X which is far away from the lens characteristic.
Define the following three-phase symmetrical quantities (the phase angle is related
to phase L1):
V V
V
V
V
ts t FwdZ
VT s
VT p
= × × = × × =0 9 0 9 11931
0 1
13 8
77 81. .
.
.
.
,
,
,
EQUATION14063 V1 EN-US (Equation 31)
Section 13 1MRK 502 073-UUS A
Testing functionality by secondary injection
168 Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062
Commissioning manual