Table 23: Calculation modes
Set value:
Mode
Formula used for complex power calculation
A, B, C
* * *
A A B B C C
S V I V I V I= × + × + ×
EQUATION2055 V1 EN-US (Equation 80)
Arone
* *
AB A BC C
S V I V I= × - ×
EQUATION2056-ANSI V1 EN-US (Equation 81)
PosSeq
*
3
PosSeq PosSeq
S V I= × ×
EQUATION2057-ANSI V1 EN-US (Equation 82)
AB
* *
( )
AB A B
S V I I= × -
EQUATION2058-ANSI V1 EN-US (Equation 83)
BC
* *
( )
BC B C
S V I I= × -
EQUATION2059-ANSI V1 EN-US (Equation 84)
CA
* *
( )
CA C A
S V I I= × -
EQUATION2060-ANSI V1 EN-US (Equation 85)
A
*
3
A A
S V I= × ×
EQUATION2061-ANSI V1 EN-US (Equation 86)
B
*
3
B B
S V I= × ×
EQUATION2062-ANSI V1 EN-US (Equation 87)
C
*
3
C C
S V I= × ×
EQUATION2063-ANSI V1 EN-US (Equation 88)
2. Adjust the injected current and voltage to the set values in % of IBase and VBase
(converted to secondary current and voltage). The angle between the injected
current and voltage shall be set equal to the set direction Angle1, angle for stage 1
(equal to 0° for low forward power protection and equal to 180° for reverse
Section 13 1MRK 502 073-UUS A
Testing functionality by secondary injection
208 Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062
Commissioning manual