HMI Signal Name: Status Description
BIMnn READY / FAIL BIM error. Binary input module Error
status. Signal activation will reset the
IED
BOMn
READY / FAIL BOM error. Binary output module Error
status.
IOMn READY / FAIL IOM-error. Input/Output Module Error
status.
MIMn READY / FAIL mA input module MIM1 failed. Signal
activation will reset the IED
RTC READY / FAIL This signal will be active when there is a
hardware error with the real time clock.
Time Sync READY / FAIL This signal will be active when the
source of the time synchronization is
lost, or when the time system has to
make a time reset.
Application
READY / FAIL This signal will be active if one or more
of the application threads are not in the
state that Runtime Engine expects. The
states can be CREATED, INITIALIZED,
RUNNING, etc.
RTE
READY / FAIL This signal will be active if the Runtime
Engine failed to do some actions with the
application threads. The actions can be
loading of settings or parameters for
components, changing of setting groups,
loading or unloading of application
threads.
IEC61850
READY / FAIL This signal will be active if the IEC 61850
stack did not succeed in some actions
like reading IEC 61850 configuration,
startup etc.
LMD
READY / FAIL LON network interface, MIP/DPS, is in
an unrecoverable error state.
LDCMxxx READY / FAIL Line Differential Communication Error
status
OEM READY / FAIL Optical Ethernet Module error status
Also the internal signals, such as INT--FAIL and INT--WARNING can be connected to
binary output contacts for signalling to a control room.
In the IED Status - Information, the present information from the self-supervision
function can be viewed. Indications of failure or warnings for each hardware module
are provided, as well as information about the external time synchronization and the
internal clock. All according to table
26. Loss of time synchronization can be
considered as a warning only. The IED has full functionality without time
synchronization.
1MRK 502 073-UUS A Section 16
Troubleshooting
Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062 299
Commissioning manual