Table 28: Hint menu
Headline Explanation
Incorrect setting of SyncLostMode There are two explanations possible:
SyncLostMode
is set to
Block
, no time source is
configured to achieve the required accuracy.
Unless a high accuracy time source is selected, the
function dependent on high time accuracy will be
blocked.
SyncLostMode
is set to
BlockOnLostUTC
, but
there is no UTC capable synch source (GPS, IRIG-
B) used. Unless a UTC capable time source is
selected, the function dependent on high time
accuracy will be blocked.
Sampled value substituted
<Access Point><Hardware Module
Identifier><svID>
Where the Hardware Module Identifier is the same
as given in PCM600, e.g. AP1: MU1_9201 svID:
<ABB_MU0101>
Time diff: IED vs Sampled value
<Access Point><Hardware Module
Identifier><svID>
Where the Hardware Module Identifier is the same
as given in PCM600, e.g. AP1: MU1_9201 svID:
<ABB_MU0101>
Frequency diff: IED vs Sampled value
<Access Point><Hardware Module
Identifier><svID>
Where the Hardware Module Identifier is the same
as given in PCM600, e.g. AP1: MU1_9201 svID:
<ABB_MU0101>
Wrong cycle time for PMU report
Wrong cycle time on SMAI or 3PHSUM block
connected to Phasor Report block. The SMAI or
3PHSUM block should have the same cycle time
as that of Phasor Report.
PMU not connected to 3ph output
The PMU phasor report input(s) must be connected
to the 3ph output of SMAI or 3PHSU.
Invalid value set for PMU Parameters There are two explanations possible:
Check if the following parameters are set correctly
on PMUREPORT:
ReportRate
or
SvcClass
or
parameter PRIMVAL:1.FrequencySel is not set as
50Hz / 60Hz.
Check if the following parameters are set correctly
on PMUREPORT:
ReportRate
or
SvcClass
or
RptTimetag
or parameter PRIMVAL:
1.FrequencySel is not set as 50Hz / 60Hz.
Invalid phase angle reference
The selected
PhaseAngleRef
corresponds to an
analog channel that is not configured. Please
configure a valid reference channel.
Table continues on next page
Section 16 1MRK 502 073-UUS A
Troubleshooting
302 Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062