RegA Typ Scale IEC 61580 name SA name Description Values
128.05 Bit < reserved > 0
128.06 Bit < reserved > 0
128.07 Bit < reserved > 0
128.08 Bit < reserved > 0
128.09 Bit < reserved > 0
128.10 Bit < reserved > 0
128.11 Bit < reserved > 0
128.12 Bit < reserved > 0
128.13 Bit < reserved > 0
128.14 Bit < reserved > 0
128.15 Bit < reserved > 0
2.3.2.4 SSR2 System status register 2 - IED mode and state
Table 80: SSR2 System status register 2 - IED mode and state
RegA Typ Scale IEC 61580 name SA name Description Values
129.00 Bit Device test mode 1=Test mode
129.01 Bit < reserved > 0
129.02 Bit Remote/Local state 0/1=Rem/Loc
Active setting group SG=1..6
129.03 Bit - bit 0
129.04 Bit - bit 1
129.05 Bit - bit 2
129.06 Bit IED timesynch failure 1=Failure
129.07 Bit < reserved > 0
129.08 Bit Last reset cause a 1=Cold start
129.09 Bit Last reset cause b 1=Watchdog
129.10 Bit Last reset cause c 1=Warm start
129.11 Bit < reserved > 0
129.12 Bit < reserved > 0
129.13 Bit < reserved > 0
129.14 Bit < reserved > 0
129.15 Bit < reserved > 0
1MRS757057 B Section 2
Modbus data mappings
REU615 45
Point List Manual