EasyManua.ls Logo

ABB Relion REC670 - 7.7 Thermal overload protection, one time constant, Celsius;Fahrenheit LCPTTR;LFPTTR

ABB Relion REC670
482 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
The fault current, in the fault point, can be calculated as:
phase
j 0
0 f
3 U
I 3I
Z 3 R
×
= =
+ ×
EQUATION1944 V1 EN-US (Equation 47)
The impedance Z
0
is dependent on the system earthing. In an isolated system (without neutral
point apparatus) the impedance is equal to the capacitive coupling between the phase
conductors and earth:
phase
0 c
j
3 U
Z jX j
I
×
= - = -
EQUATION1945 V1 EN-US (Equation 48)
Where
I
j
is the capacitive earth fault current at a non-resistive phase-to-earth fault
X
c
is the capacitive reactance to earth
In a system with a neutral point resistor (resistance earthed system) the impedance Z
0
can be
calculated as:
c n
0
c n
jX 3R
Z
jX 3R
- ×
=
- +
EQUATION1946 V1 EN-US (Equation 49)
Where
R
n
is the resistance of the neutral point resistor
In many systems there is also a neutral point reactor (Petersen coil) connected to one or more
transformer neutral points. In such a system the impedance Z
0
can be calculated as:
( )
n n c
0 c n n
n c n n c
9R X X
Z jX // 3R // j3X
3X X j3R 3X X
= - =
+ × -
EQUATION1947 V1 EN-US
(Equation 50)
Where
X
n
is the reactance of the Petersen coil. If the Petersen coil is well tuned we have 3X
n
= X
c
In this case the
impedance Z
0
will be: Z
0
= 3R
n
Now consider a system with an earthing via a resistor giving higher earth fault current than the
high impedance earthing. The series impedances in the system can no longer be neglected.
The system with a single phase to earth fault can be described as in Figure
64.
Section 7 1MRK 511 358-UEN A
Current protection
136
Application manual

Table of Contents

Related product manuals