Section 3 1MAC309294-MB F
Basic functions
60 RER620
Technical Manual
The CL output signal indicates that the position is closed. Default value (0) is used if
VALID output indicates invalid status.
The OK output signal indicates that the position is neither in faulty or intermediate state.
The default value (0) is used if VALID output indicates invalid status.
3.9.5.3 Signals
Table 47: GOOSERCV_INTL Input signals
Table 48: GOOSERCV_INTL Output signals
3.9.6 GOOSERCV_CMV function block
3.9.6.1 Function block
Figure 14: function block
3.9.6.2 Functionality
The GOOSERCV_CMV function is used to connect GOOSE measured value inputs to the
application. The MAG_IN (amplitude) and ANG_IN (angle) inputs are defined in the
GOOSE configuration (PCM600).
The MAG output passes the received GOOSE (amplitude) value for the application.
Default value (0) is used if VALID output indicates invalid status.
The ANG output passes the received GOOSE (angle) value for the application. Default
value (0) is used if VALID output indicates invalid status.
3.9.6.3 Signals
Table 49: GOOSERCV_CMV Input signals
Name Type Default Description
IN Dbpos 00 Input signal
Name Type Description
OP BOOLEAN Position open output signal
CL BOOLEAN Position closed output signal
OK BOOLEAN Position OK output signal
VALID BOOLEAN Output signal
GOOSERCV_CMV
MAG
ANG
VALID
Name Type Default Description
MAG_IN FLOAT32 0 Input signal (amplitude)
ANG_IN FLOAT32 0 Input signal (angle)