4-86 ADS TRITON+
®
Manual
z Entity Select the data entity whose value you want the XIO
device to output as an analog signal. While the list contains all
entities, choose only those entities which the monitor is
currently generating.
z Min Value Enter the data value (for the selected entity) which
will correspond to the weakest analog output signal. The Min
Value will be used to translate actual data into analog output
signals and should correspond to the lowest possible entity
value (weakest) in the scale (4mA).
z Max Value Enter the data value (for the selected entity)
which will correspond to the strongest analog output
signal. The Max Value will be used to translate actual data
values into analog output signals and should correspond to the
highest possible entity value (strongest) in the scale (20mA).
z Manual Enter the value to use when manually testing the
analog output signal. This value will be used with the Enable
Manual checkbox for testing the analog output signal.
Important: Be sure to activate the monitor after
changing the Manual or Enable Manual parameter in
order for the new parameter to take effect.
z Enable Manual Select this checkbox when you want to
manually test the analog output signal to output the value
designated in the Manual field.
Digital Input 1 (2) Configure the following values for each
digital input device (maximum of two) connected to the XIO
device.
z Entity Select DI1 (DI2) from the drop-down list to enable the
associated digital input device connected to the XIO device.
z Store Data Select this checkbox to store the most current
digital input value (0 or 1) at each monitor wakeup to the
monitor as DI1 (DI2). Digital input channels are scanned
continuously, however, only the most current input signal is
stored at the monitor sample interval.
Digital Output 1 (2) Configure the parameter for the Digital
Output device.

Table of Contents