8-2 ADS TRITON+ Manual
Installing the Inclinometer
Follow the steps below to install the ADS Inclinometer sensor.
Note: The Inclinometer sensor should not be connected
to the ADS TRITON+ monitor until it is installed onto the
flood gate.
Note: If the default 25’ (7.6m) length of the Inclinometer
cable is not sufficient for the installation, order an
extension cable (ADS P/N 8000-0044-25).
Note: Manhole and sewer system work involves confined
space entry and is inherently dangerous. Therefore,
installers and technicians must comply with all federal,
state, and municipal regulations concerning confined space
entry. ADS is not responsible for any injuries, damages,
claims, or liability resulting directly or indirectly from the
use of this installation guide or the installation of any ADS
equipment.
1. Ensure the flood gate is in the closed position.
2. Position the ADS Inclinometer sensor vertically or
horizontally on the flood gate or to a flat, level surface
attached to the flood gate. See the following illustrations
for recommended installation positions.