INSTALLER menu - SYSTEM SIDE submenu - Pump sengs (Page 1)
INSTALLER menu - SYSTEM SIDE submenu - Pump sengs (Page 2)
ACTIONS
AVAILABLE:
ACTIONS
AVAILABLE:
A
Return to the submenu selection page for the
INSTALLER menu
B
Go to alarm menu
C
Go back to previous page
D
Sets the number of pumps installed on the system side.
The number of pumps can be 2 at maximum (in case of
water/water machines in heang, this page is used to
dene the number of system side pumps)
E
Sets the delay for compressor switch-on aer switching
on the system side pumps
F
Sets the delay switch-o of pumps on the system side
aer switching o the compressors
A
Return to the submenu selection page for the
INSTALLER menu
B
Go to alarm menu
C
Go back to previous page
D
Sets the number of working hours aer which the
main pump is replaced by the backup pump and vice
versa. Aer the number of hours set, the pumps will
be inverted as soon as all the compressors are inacve.
First the pump will be switched o, then there will be a
stop, equal to the waing me specied in parameter
(
E
), aer which the backup pump will be started as
main pump
E
Sets the waing me during the pump reversing stage
F
Sets how many days before forcing pump inversion in
the event that the unit never has compressors stopped
G
Sets use of the system side pumps to perform the
anfreeze funcon when required