32
INSTALLER menu - OPTIONS submenu - Sengs related to the BMS
INSTALLER menu - OPTIONS submenu - TBX/WTX/WTG mulfuncon input sengs
ACTIONS
AVAILABLE:
ACTIONS
AVAILABLE:
A
Return to the submenu selection page for the
INSTALLER menu
B
Go to alarm menu
C
Go to next page
D
Sets the address to be assigned to the BMS1 (i.e.
accessory AER485P1)
E
Sets the protocol to be used for the BMS1. The
available protocols are:
MODBUS;
CAREL;
LON WORKS (currently not available);
pCOweb;
F
Sets the communicaon speed for the BMS1
G
Sets the address to be assigned to the BMS2 (i.e.
accessory AERNET)
H
Sets whether to enable the ON/OFF command from an
external BMS supervisor
A
Return to the submenu selection page for the
INSTALLER menu
B
Go to alarm menu
C
Go to next page
D
Go back to previous page
E
Sets the funcon to be assigned to the analogue input
U7. The funcons can be:
NONE = mulfuncon input not used;
POWER LIMIT = based on the signal applied to the
analogue input U7, a value will be established to be
applied to the power request limit by the system;
POWER REQUEST = based on the signal applied to the
analogue input U7, the power request that the unit
must meet will be established;
SETPOINT = based on the signal applied to the
analogue input U7, the value of the setpoint to be
applied to the unit will be established;
F
Sets the type of signal applied to the analogue input
U7. The signals managed can be:
0-10V = signal in 0-10V voltage;
4-20mA = signals in 4-20mA current;
NTC = signal from NTC temperature probe;
G
To enable the U7 mulfuncon input, it is required
to operate on the digital input ID14. It is possible
to choose the state with which to enable use of the
mulfunconal input:
CLOSED = if ID14 is closed the U7 input open;
OPEN = if ID14 is open the U7 input enabled;