Rockwell Automation Publication 2094-UM001J-EN-P - March 2017 105
Connect the Kinetix 6000 Drive System Chapter 5
Wire the Motor Power (MP) Connector
Connections to the motor power (MP) connector include rotary motors, 
linear motors, and motor driven actuators.
This example applies to AM modules and the inverter section of IAM 
modules.
Figure 54 - IAM/AM Module (MP connector)
Cable Shield Terminations
Factory-supplied Bulletin 2090 motor power cables for motors and actuators 
are shielded, and the braided cable shield must terminate at the drive during 
installation. A small portion of the cable jacket must be removed to expose the 
shield braid. The exposed area must be clamped (with the clamp provided) on 
top of the IAM or AM modules and the power wires terminated in the motor 
power (MP) connector plug.
ATTENTION: Make sure the motor power connections are correct when 
wiring the MP connector plug and that the plug is fully engaged in the 
module connector. Incorrect wiring/polarity or loose wiring can cause 
explosion or damage to equipment.
Cable Shield Clamp
Kinetix 6000 
IAM/AM Module
(IAM module is shown)
Slide-open
Pivot-open
SHOCK HAZARD: To avoid hazard of electrical shock, make sure shielded 
power cables are grounded at a minimum of one point for safety.
IMPORTANT For TL-Series™ motors, also connect the 152 mm (6.0 in.) termination wire to 
the closest earth ground. 
Refer to Pigtail Terminations on page 106
 for more information.