EasyManua.ls Logo

Allen-Bradley 2094-AC05-MP5 - Cable Categories for Kinetix 6000 Systems

Allen-Bradley 2094-AC05-MP5
290 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Rockwell Automation Publication 2094-UM001J-EN-P - March 2017 45
Plan the Kinetix 6000 Drive System Installation Chapter 2
Observe these guidelines when installing your Logix5000™ Sercos interface
module:
The clean zone (C) is beneath the less noisy modules (I/O, analog,
encoder, registration, an so forth (gray wireway).
The dirty zone (D) is above and below the power supply and noisy
modules (black wireway).
The Sercos fiber-optic cables are immune to electrical noise, but due to
their delicate nature, route them in the clean zone.
Figure 18 - Noise Zones (ControlLogix chassis)
Cable Categories for Kinetix 6000 Systems
These tables indicate the zoning requirements of cables connecting to the
Kinetix 6000 drive components.
Table 14 - IAM Module (converter side)
(1)
D
D
C
AC Line
Filter
Spare Slots
Dirty Wireway
Clean Wireway
Route dirty wireways directly above the ControlLogix controller chassis
(shielded by the chassis).
Line Filter/Power Supply
Connections Segregated
(not in wireway)
Dirty I/O
(24V DC I/O, AC I/O)
Clean I/O
(Analog, Encoder
Registration)
Wire/Cable Connector
Zone Method
Very
Dirty
Dirty Clean
Ferrite
Sleeve
Shielded
Cable
CTRL 1 and 2 CPD X
DC-/DC+ (unshielded cable)
IPD
X
L1, L2, L3 (shielded cable) X X
L1, L2, L3 (unshielded cable) X
CONT EN- and CONT EN+ (M1 contactor) CED X
DPI DPI X X

Table of Contents