Rockwell Automation Publication 2094-UM001J-EN-P - March 2017 23
Start Chapter 1
CE Requirements (system with LIM module)
To meet CE requirements when your Kinetix 6000 system includes the LIM 
module, follow all the requirements as stated in CE Requirements (system 
without LIM module) and these additional requirements as they apply to the 
AC line filter.
• Install the LIM module (catalog numbers 2094-AL09 or 2094-BL02) as 
close to the IAM module as possible.
• Install the LIM module (catalog numbers 2094-ALxxS, 2094-BLxxS, or 
2094-XL75S-Cx) with line filter (catalog number 2090-XXLF-xxxx) as 
close to the IAM module as possible.
When the LIM module (catalog numbers 2094-ALxxS, 2094-BLxxS, or 
2094-XL75S-Cx) supports two IAM modules, each IAM module 
requires an AC line filter installed as close to the IAM module as 
possible.