56 Rockwell Automation Publication 440R-UM012E-EN-P - November 2018
Appendix A Specifications
Auxiliary Signal
Table 15 - Auxiliary Signal
Single Wire Safety Input
Signal
Table 16 - Single Wire Safety Input Signal
Attribute 440R-GL2S2P
Output signals Y32
Continuous output current, max 50 mA
ON state voltage drop (P/S to +), max 0.2V
Surge output current, max 700 mA
Surge output current duration, max 5 ms
Load capacitance, max 1 µF
OFF state leakage current, max < 0.1 mA
Short-circuit detection No
Short-circuit protection Yes
Galvanic isolation: I/O from logic No
Attribute 440R-GL2S2P
Input signals L12
ON voltage, max 26.4V
ON voltage, min 11V
OFF voltage, max 5V
OFF current, max 2 mA
ON current at 24V DC, max 11.0 mA
ON current at 26.4V DC, max 11.1 mA
Galvanic isolation: I/O from logic No
Overvoltage protection Yes
Reverse voltage protection Yes
Input capacitance 10 nF