60 Rockwell Automation Publication 440R-UM012E-EN-P - November 2018
Appendix B Regulatory Approvals
SIL Rating
The GLP safety relay meets the requirements of SIL CL 2 in accordance with
IEC/EN 61508 and IEC 62061.
Table 20 - SIL Rating
Performance Level/Category
The GLP safety relay can be used in safety systems that meet up to Category 3
and Performance Level PLd in accordance with ISO 13849-1.
Table 21 - Performance Level
EMC Directive
This product is designed and tested to meet the European Council Directive
2015/30/EU on Electromagnetic Compatibility (EMC) and the following
standards:
EN 61000-6-4: Generic Standards — Emission Standard for Industrial
Environments
EN 61000-6-2: Generic Standards — Immunity for Industrial
Environments
This product is intended for use in an industrial environment.
Attribute 440R-GL2S2P
Safety Integrity Level Claim Limit 2
PFD 4.13E-09
PFH 7.19E-9
Mode of Operation High Demand
Hardware Fault Tolerance 1
Safe Failure Fraction 98.95%
Attribute 440R-GL2S2P
Category Up to 3
Performance Level Up to d
MTTFd 378
DC Avg 97.66%
Mission Time (a) 20
Days Of Operation (d) 365
Hours of Operation (h) 24
T cycle (h/s) 8/28.8

Table of Contents