Publication 1763-RM001B-EN-P - April 2007
376 Communications Instructions
In this example, the controller reads 10 elements from the target’s (Local
Node 2) N7 file, starting at word N7:50. The 10 words are placed in the
controller’s integer file starting at word N7:0. If five seconds elapse before
the message completes, error bit MG11:0/ER is set, indicating that the
message timed out.
Valid File Type Combinations
Valid transfers between file types are shown below for MicroLogix
messaging:
Example 2 - Local Read from a 485CIF
Message Instruction Setup
Local Data Types Communication Type Target Data Types
O
(1)
, I
(1)
, B, N, L
(1) Output and input data types are not valid local data types for read messages.
<---> read/write O, I, S, B, N, L
T <---> read/write T
C <---> read/write C
R <---> read/write R
RTC
(2)
(2) 500CPU write RTC-to-Integer or RTC-to-RTC only.
---> write N, RTC
ST
(3)
(3) MiroLogix 1100 OS Series B FRN 4 or later.
<---> read/write
ST
(3)
efesotomasyon.com - Allen Bradley,Rockwell,plc,servo,drive

Table of Contents

Other manuals for Allen-Bradley MicroLogix 1100

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley MicroLogix 1100 and is the answer not in the manual?

Allen-Bradley MicroLogix 1100 Specifications

General IconGeneral
Processor32-bit
Programming SoftwareRSLogix 500
MountingDIN rail or panel mount
Power Supply24V DC
TypeCompact PLC
Digital Inputs12
Digital Outputs8
Analog Inputs4 (depending on model)
Analog OutputsOptional with expansion module
Programming LanguageLadder Logic
Operating Temperature0 to 55 °C (32 to 131 °F)
SeriesMicroLogix

Related product manuals