10-2 Communicating with Devices on a Serial Link
Configuring the Controller
Serial Port
Channel 0 is the serial port and is configurable for RS-232C, RS-423, or
RS-422A compatible communication. Use switch assembly SW2 to specify the
serial port configuration.
To set the controller switch, see chapter 23 or look on the side label of the
controller, which shows the switches in switch assembly SW2 and a table
listing the settings.
Using Channel 0
You can use the controller’s serial port (channel 0) to connect the controller to
devices that:
can send and receive ASCII characters by using User mode (ASCII
communication)
communicate using DF1 protocol by using one of three available System
modes
User Mode
In user mode, all data are received and sent via a buffer. To access or send this
data, use ASCII instructions in your ladder program. The ASCII data a PLC-5
controller sends contain no additional protocol characters.
In user mode, only ASCII instructions can be used. If you try to use a message
(MSG) instruction that references the serial port, the error (.ER) bit is set.
Examples of ASCII peripheral devices are:
ASCII terminals
Bar code readers
Allen-Bradley Dataliners
Weigh scales
Printers
System Mode
In system mode, the controller interprets a command from another device.
Use system mode when you need to communicate with other devices on a link.
System mode, with DF1 protocol, is a separate and unique communication
link from the DH+ link.

Table of Contents

Other manuals for Allen-Bradley PLC-5

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley PLC-5 and is the answer not in the manual?

Allen-Bradley PLC-5 Specifications

General IconGeneral
Programming SoftwareRSLogix 5
Programming LanguagesLadder Logic
Power Supply120/240V AC or 24V DC
Communication PortsDH+, Remote I/O, Ethernet/IP, ControlNet
Operating Temperature0 to 60°C (32 to 140°F)
Relative Humidity5 to 95% non-condensing
MemoryUp to 64K words (user program and data)

Related product manuals