EasyManua.ls Logo

Allen-Bradley PLC-5 - Appendix B; S:3-10

Allen-Bradley PLC-5
388 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Publication 1785-UM012D-EN-P - July 2005
Processor Status File B-3
S:3-10
This Word Stores
S:3 to S:6 Active Node table for channel 1A
Word
BitsDH+ Station #
30-1500-17
40-1520-37
50-1540-57
60-1560-77
S:7 Global status bits: (See also S:27, S:32, S:33, S:34, and S:35)
S:7/0-7 rack fault bits for racks 0-7
S:7/8-15 unused
S:8 Last program scan (in ms)
S:9 Maximum program scan (in ms)
S:10Minor fault (word 1)
See also S:17
S:10/00 Battery is low (replace in 1-2 days)
S:10/01 DH+ active node table has changed
S:10/02 STI delay too short, interrupt program overlap
S:10/03 memory module transferred at power-up
S:10/04 Edits prevent SFC continuing; data table size changed during
program mode; reset automatically in run mode
S:10/05 Invalid I/O status file
S:10/06 reserved
S:10/07 No more command blocks exist to execute block-transfers
S:10/08 Not enough memory on the memory module to upload the program
from the controller
S:10/09 No MCP is configured to run
S:10/10 MCP not allowed
S:10/11 PII word number not in local rack
S:10/12 PII overlap
S:10/13 no command blocks exist to get PII
S:10/14 Arithmetic overflow
S:10/15 SFC “lingering” action overlap - step was still active when step
was reactivated