Operation  Sorensen SGI Series 
3-42  M550221-01 Rev U 
Shutdown fault.  This terminal goes to high state in the event of 
converter, temperature, overvoltage or bias supply fault.  A 
7-13.3 VDC signal can be applied to this pin to shutdown the output 
of the unit. An 8 VDC minimum output signal is provided into a 
10 kminimum load, in the event of an internally generated 
shutdown. Circuit return Pin J1-6 (COM). See Section 3.13.3. 
Output voltage monitor.  0-10 VDC equals to 0-100% rated voltage. 
Minimum load resistance 100 kCircuit return Pin J1-6 (COM). 
Voltage programming return.  Used with Pins J1-9, J1-15 or J1-21 
and must be referenced to Pin J1-6 (COM) circuit common. 
1 mA current source for remote voltage programming using 
resistance.  0-5 kΩ resistor referenced to Pin J1-4 or Pin J1-20 
(VP RTN) will program the output voltage from 0-100%.  See 
Section 3.11. 
1 mA current source for remote current programming using 
resistance.  0-5 kΩ resistor referenced to Circuit return Pin J1-23 or 
Pin J1-25 (IP RTN) will program the output current from 0-100%. 
See Section 3.10. 
Current programming return.  Used with Pins J1-10, J1-16 or J1-22 
and must be referenced to Pin J1-6 (COM) circuit common. 
Circuit common connected to Pin J1-6. Same potential as the 
negative output terminal. 
Current programming return.  Used with Pins J1-10, J1-16 or J1-22 
and must be referenced to Pin J1-6 (COM) circuit common. 
†
 With  the  Remote  Isolated  Analog  Interface  control  (option),  the  control  ground  is  isolated  from 
output power (output negative terminal).  See Section 1.2.2 and Section 3.15.  
*
 Signals not available with Remote Isolated Analog Interface control (option). 
Table 3–5. Analog Control Connector (J1), Designations and Functions