66
ASSA ABLOY Hospitality
66 8003 016-3
To set up the online network
The online network for the above example looks as in Figure C22. The three
thermostats 1021, 1022 and 1023 must be set up under the same parent in the
network, i.e. be set up in the same PAN (personal area network). To set up the
network, follow the steps below:
1. Double click on SysMon.exe in the Visionline installation folder to open
SysMon (System Monitor) which is used for managing the online network.
2. Log on to SysMon; go to File/Log on and enter user ID and password. At
'Operator card', choose the applicable card encoder and click Enter.
3. Go to View/Online Network to show the Online Network tree.
4. Install the gateway; see User manual Online option for details.
5. Initialize thermostat 1021 with "regular parameters", i.e. all parameters except
for those related to suite. To do this, use the Initialize alternative in Orion
Service but leave the Suite settings empty. See Daily use manual Orion EMS
for details about Initialize.
6. Connect thermostat 1021 to the gateway; see chapter 5
for details.
7. Connect motion sensor 1021 to thermostat 1021; see chapter 5
for details.
8. Connect lock 102 to thermostat 1021; see chapter 5
for details.
9. Repeat steps 5-7 for the devices in rooms 1022 and 1023 respectively.
10.Initialize thermostat 1021 with suite settings; click here
for details.
11.Initialize thermostat 1022 with suite settings; click here
for details.
12.Read out the thermostat status for thermostat 1021; click here
for details.
13.Read out the thermostat status for thermostat 1022; click here
for details.
14.See Figure C32
for a picture of the final Online Network tree.
Figure C22