For version with MWG within actuator
Setting of limit and torque switching via local controls
Galvanically isolated analogue output 0/4 – 20 mA (load max. 500 Ī©).Torque feedback signal
TPCHA000-1AF-A000 TPA00R100-0I1-000, 3-ph; 380 V – 480 V
TPCHA000-1AE-A000 TPA00R100-0I1-000, 1-ph; 220 V – 240 V
Wiring diagram (basic version)
Settings/programming the Profinet interface
The Profinet interface is set (assignment of device name as well as assignment of the IP address) using the Profinet engineering tools of
the DCS.
General data of the Profinet interface
Profinet according to IEC 61158 and IEC 61784Communication protocol
Star topology, point-to-point wiring
Due to the switch function integrated within the AC 01.2, both line topology and redundant ring topology
(MRP) are available.
Unused network ports can be switched off.
Network topology
Ethernet IEEE 802.3
2-pair cabling in compliance with IEC 61784-5-3 Auto Polarity Exchange, Auto Negotiation and Auto
Crossover are supported.
Connection
2 x Ethernet connection terminals with insulation displacement connection, integral screen with strain
relief, suitable for all Ethernet cable types or 2 x RJ-45
Connection via connector for field assembly, one RJ-45 connector for Cat.5 (K009.706) is included in
the scope of supply of the electrical connection.
Profinet connection
100 Mbits/s (100BASE-TX), full duplexTransmission rate
Max. 100 mCable length
I/O controller (usually the PLC/DCS)
I/O devices (field devices)
I/O supervisor (programming device, PC or HMI for diagnostics/commissioning)
Device classes
Provider - consumer modelFieldbus access
Version V2.32Supported Profinet specification
Cyclic Profinet communication (RT)
Acyclic Profinet communication (Read/Write Record)
Supported Profinet functions
Status Alarm
Update Alarm
Port Data Change Notification Alarm
Sync Data Change Notification Alarm
Supported Profinet alarms
ACD (Address Conflict Detection)
ARP (Address Resolution Protocol)
DCP (Discovery and Basic Configuration Protocol)
SNMP (Simple Network Management Protocol)
LLDP (Link Layer Discovery Protocol) in accordance with IEEE 802.1AB
These functions allow assignment of the Profinet device name, a graphic representation of the plant to-
pology, port-granular diagnostics as well as neighbourhood detection as the basis for quick commissioning
and easy device replacement.
Supported network diagnostic and
management protocols
Media Redundancy Protocol in compliance with IEC 62439 (switch function integrated within
AC 01.2)
Standard:Profinet redundancy
System redundancy S2 Single NAPOption:
319Vendor ID
1Ident Code
AUMA-Actuator-AC01-2Profinet device type
62976I&M0 Profile ID:
4I&M0 Profile Specification Type:
257I&M0 Version:
30I&M0 Supported:
Identification & Maintenance proper-
ties
0x013F; 0x0001Profinet Ident Nr.
79
SQV 05.2 – SQV 14.2 / SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
ACV 01.2 Non-Intrusive Profinet Technical data