General data of the Profinet interface
0x80010000DAP (Device Access Point)
CC-B (Conformance Class B) for the Profinet application of the AC actuator controls
CC-C (Conformance Class C) for the integral switch function
Conformance class
IIINetload Class
Via TCP/IP and integral web server possible
Via FDI package & software for diagnostics/commissioning (e. g. Siemens PDM, Emerson AMS)
Device diagnostics via Ethernet
Via GSD (ml) file (available for download at www.auma.com)Device integration
Commands and signals of the Profinet interface
OPEN, STOP, CLOSE, position setpoint, RESET, EMERGENCY operation command, enable local
controls, Interlock OPEN/CLOSE, PVST
Process representation output
(command signals)
End positions OPEN, CLOSED
Actual position value
Actual torque value, requires MWG in actuator
Selector switch in position LOCAL/REMOTE
Running indication (directional)
Torque switches OPEN, CLOSED
Limit switches OPEN, CLOSED
Manual operation by handwheel or via local controls
Analogue (2) and digital (4) customer inputs
Process representation input
(feedback signals)
Motor protection tripped
Torque switch tripped in mid-travel
One phase missing
Failure of analogue customer inputs
Process representation input
(fault signals)
The behaviour of the actuator is programmable:
●
Stop in current position
●
Travel to end position OPEN or CLOSED
●
Travel to any intermediate position
●
Execute last received operation command
Behaviour on loss of communication
Service conditions
Indoor and outdoor use permissibleUse
Any positionMounting position
≤ 2 000 m above sea level
> 2,000 m above sea level on request
Installation altitude
Refer to name plate of actuator controlsAmbient temperature
Up to 100 % relative humidity across the entire permissible temperature rangeHumidity
IP68Standard:Enclosure protection according to
EN 60529
DS terminal compartment additionally sealed against interior of actuator controls (double
sealed)
Option:
According to AUMA definition, enclosure protection IP68 meets the following requirements:
●
Depth of water: maximum 8 m head of water
●
Duration of continuous immersion in water: Max. 96 hours
●
Up to 10 operations during continuous immersion
●
Modulating duty is not possible during continuous immersion.
For exact version, refer to actuator controls name plate.
Pollution degree 4 (when closed), pollution degree 2 (internal)Pollution degree according to IEC
60664-1
1 g, from 10 Hz to 200 Hz
Resistant to vibration during start-up or for failures of the plant. However, a fatigue strength may not be
derived from this. (Not valid in combination with gearboxes)
Vibration resistance according to
IEC 60068-2-6
KS: Suitable for use in areas with high salinity, almost permanent condensation, and high
pollution.
Standard:Corrosion protection
KX: Suitable for use in areas with extremely high salinity, permanent condensation, and
high pollution.
Option:
80
SQV 05.2 – SQV 14.2 / SQRV 05.2 – SQRV 14.2 Control unit: electronic (MWG)
Technical data ACV 01.2 Non-Intrusive Profinet