System Topology
Configuration Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-CONFIG/EGB, Rev. A, 2013-04-03,
Autronica Fire and Security AS
Page 110
7.5 Clear Loop Config. – Restart System
This command allows you to delete all points on a selected detection
loop.
The command is useful in the following cases
:
When major changes are to be done on an existing detection
loop, i.e. a large amount of points on a detection loop are to be
removed and others are to be added.
The advantage: you do not have to accept points - one by one –
that are removed before the new configuration is saved. Fault
messages will not appear after system restart.
When the configuration of a detection loop is not completed by
the end of the day, and the service technician intends to complete
the configuration of this detection loop the next day, executing this
command will save the configuration and the detection loop in
question will be fully functional and resume normal operation after
system restart. The technician can complete the configuration the
next day without dealing with unnecessary fault messages.
Expanding a system:
If a loop is to be moved from one panel to another, all topology
information for this loop on the replaced panel will be deleted.
Note that the Clear Loop Config. – Restart System command will not
affect the detectors’ Performance Class settings. For example, an
optical detector that has been set to “Industrial” will still have this
setting after the command is executed.
From the Service Menu, perform the following:
Use the arrow down button to scroll downwards to
System Topology, then press Enter.
A list appears, including all loops and the panel bus.
Use the arrow button to select the panel bus or the loop.
Press the Function button
Use the arrow down button to select Clear Loop Config. –
Restart System, then press Enter.
The following message will appear:
“The configuration related to any unit on this loop will be deleted and
the loop will be completely restarted.”
Use the left arrow button to select Accept, then press Enter.
NOTE: All existing configuration on the selected detection loop will
be deleted.