Error Counts
[0]
U
Description This menu provides a diagnostic view of meter performance. Below are
several system diagnostic counters and their definitions. Use discretion when
interpreting these counters. These values could be altered during system setup
or when using the verification device. We suggest that you reset these counters
before you start monitoring your system and look for conditions possibly
affecting performance.
Sensor The number of times an invalid sensor condition has been observed.
Empty Pipe The number of times an empty pipe condition has been observed by the meter.
Full Scale The number of times the flow has exceeded the Full Scale Flow setting.
Totalizer The number of times the totalizers have exceeded limits of the meter.
Pulse Sync. The number of times the pulse outputs have fallen out of synchronization.
ADC Interrupt The number of times an analog input measurement has been missed.
ADC Range The number of times the analog input measurement range has been exceeded.
System Error A diagnostic system message indicating the reason for a system reset.
System Resets The number of times the meter has been reset.
System Reset
ID
Diagnostic information about a system reset as a result of expired
internaltimers.
Token Errors Indicates the number of parameter copies from a memory token that failed to
be copied to the meter.
Checksum For MID meters. If data corruption to the meter memory occurs, this counter indicates the
memory region that is corrupted.
PowerUp Counter
[Not applicable]
U
The number of times that the unit has been powered on.
Power Off Totalizer
[Not applicable]
U
The length of time that the unit has been without power.
Version Info
[Not applicable]
U
The current software version.
Serial Number
[Not applicable]
U
The manufacturing serial number in the format YYMM####, where YYMM indicates year and
month of manufacturing and #### indicates the sequencenumber.
Meter Tag Name For Profibus – This parameter is only programmable over external Profibus communications.
Daughterboard
Information
Describes current version of attached daughterboard.
OTE: N RS485 daughterboard is not recognized because it is a pass-through device rather than
an intelligent protocol converter like HART-to-Modbus.
Polarization Voltage Diagnostic voltage to help determine if the meter or application is performing optimally.
Using the Main Menu Programming Options
Page 55 March 2022 MAG-UM-01272-EN-21