5 Integration
IO-Link state
In the IO-Link state, the momentary status of each port is displayed:
0x_0 = port disabled
0x_1 = port in std dig in
0x_2 = port in std dig out
0x_3 = port in communication OP
0x_4 = port in communication COMSTOP
0x1_ = watchdog detected
0x2_ = internal Error
0x3_ = invalid Device ID
0x4_ = invalid Vendor ID
0x5_ = invalid IO-Link version
0x6_ = invalid Frame Capability
0x7_ = invalid Cycle Time
0x8_ = invalid PD in length
0x9_ = invalid PD out length
0xA_ = no device detected
Sensor short circuit
Feedback as to the port at which a sensor supply short circuit is pending.
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Port 7
Port 6
Port 5
Port 4
Port 3
Port 2
Port 1
Port 0