To enable the upload flag of an IO-Link device,
the value 0x05 must be entered in the index 0x02, subindex 0.
(Parameterization, see IO-Link Service Data on the next page)
The upload flag is needed to overwrite already saved data in the parameter server with new
parameter data of the same IO-Link device
This function is a supplement to an output configuration of the respective port pin.
For each port pin, a safe status can be predefined which is to be assumed in the event of
a loss of bus communication.
The following values are possible for the settings:
0x00: 0
0x01: 1
0x02: last state