Parameter
Parameter manual b maXX
®
1000
Document no. 5.07004.03
105
of 208
4
Example 3: Use of bias and gain for use of full range
This example also shows a popular method. The whole scale of the potentiometer can be
used as desired. In addition to signals of 0 to 10 V, the popular voltage signals also in-
clude signals of 0 to 5 V, or any value under 10 V. Regarding the setting, please refer to
the following examples.
Example 4: Use of 0 to 5 V potentiometer range via gain adjustment
This example shows a potentiometer range of 0 to 5 Volts. Instead of adjusting gain as
example below, you can set ZP0033 to 120 Hz to achieve the same results.
ZP0033= 60 Hz
ZP1158= 20.0 %
ZP1159= 0
ZP1160= 83.3 %
ZP1161= 0
Gain ZP1160:
Bias adjustment ZP1158:
ZP0033= 60 Hz
ZP1158= 0.0 %
ZP1159= 0
ZP1160= 200 %
ZP1161= 0
Gain ZP1160:
10V
10V 2V+
-------------------------
100% 83 3%,=
10Hz
60Hz
--------------
Gain
100%
---------------
---------------
100% 20%=
10V
5V
-----------
100% 200%=