Parameter description
Parameter manual b maXX
®
1000
Document no. 5.07004.03 Baumüller Nürnberg GmbH
152
of 208
4.3
P2141
This parameter together with ZP2148 (DIP switch multiplier) determines the CAN ad-
dress.
If ZP2148 = 0, ZP2141 default value is 21.
If ZP2148 > 0, ZP2141 = ZP2141
ZP2148
ZP0870 (b maXX
®
1000 CAN address) is equal to the value of ZP2141, if the DIP
switch setting is 1.
ZP2148 = 0
ZP2148 > 0
P2141
Adresse-Einstellung für DIP-Schalter 1 0 to 127
EE Address setting for DIP switch 1 21
STOP BM_u_CANBaudrateWithSwitchOn1 1:1 -
DIP switch DIP switch value CAN address setting Default value
1 2 3
1 0 0 1 ZP2141 21
0 1 0 2 ZP2142 22
1 1 0 3 ZP2143 23
0 0 1 4 ZP2144 24
1 0 1 5 ZP2145 25
0 1 1 6 ZP2146 26
1 1 1 7 ZP2147 27
DIP switch DIP switch value CAN address setting Default value
1 2 3
1 0 0 1 ZP2141 1 ZP2148
0 1 0 2 ZP2142 2 ZP2148
1 1 0 3 ZP2143 3 ZP2148
0 0 1 4 ZP2144 4 ZP2148
1 0 1 5 ZP2145 5 ZP2148
0 1 1 6 ZP2146 6 ZP2148
1 1 1 7 ZP2147 7 ZP2148