Function
17
NGRM7xx_D00292_07_M_XXEN/02.2022
3.3.2 Recommended R
NGR
for system voltage U
sys
> 4300 V
(HRG system)
Tab. 3.2: Recommended R
NGR
for system voltage U
sys
> 4300 V (HRG system)
CD14400 CD25000
U
sys
6000 V 6600 V 7200 V 11000 V 14400 V 25000 V
I
NGR
1 A
——————
5 A
693 762 831 1270 1663 —
10 A
346 381 416 635 831 1443
15 A
231 254 277 423 554 962
20 A
(173 Ω) 191 208 318 416 722
25 A
(139 Ω) (152 Ω) (166 Ω) 254 333 577
30 A
(115 Ω) (127 Ω) (139 Ω) 212 277 481
40 A
(87 Ω) (95 Ω) (104 Ω) (159 Ω) 208 361
50 A
— (76 Ω) (83 Ω) (127 Ω) (166 Ω) 289
100 A
————(83 Ω) (144 Ω)