7.12 Info (menu 9)
The current settings of the NGRM7… can be viewed in the Info menu. Navigate through
the different views using the arrow buttons:
Device name, serial number, article number
Software Measurement equipment software version, HMI software version
Clock Time, date, summer time
Ethernet IP address, DHCP status, MAC address
7.13 Alarm (menu 10)
Acknowledge Mute buzzer, delete message from the standard display, fault message
remains stored in the history memory. If the installation is de-energized, no
restart attempts will take place.
Reset Mute buzzer, delete message from the standard display, fault message
remains stored in the history memory. If the installation is de-energized,
restart attempts will be carried out, which will only be successful after the fault
has been eliminated. The device returns to the standard display.
Test Since the relays are not monitored in the hardware or software, the relays
must be tested at regular intervals on proper functioning. The frequency of
the test cycle is subject to the safety requirements of the operator but it must
be carried out at least every six months.
During the test it must be ensured that the relays can actually switch! The
following settings are required:
Ground-fault relay menu 6.6.1.2 relay test "on"
NGR-fault relay menu 6.6.2.2 relay test "on"
Trip relay menu 6.6.3.2 relay test "on"