Modbus RTU (menu 7.3.5)
Settings for communication with other devices via Modbus RTU.
Address (menu 7.3.5.1): 1…247
Baud rate (menu 7.3.5.2): the selectable options are
9.6 kbaud,
19.2 kbaud,
38.4 kbaud,
57.6 kbaud
Parity: the selectable options are "even", "uneven", "none"
Stop bits: the selectable options are "1", "2", "auto"
5)
Brightness (menu 7.5.1)
Adjust the display brightness between 0…100 % in steps of 10. If no button is pressed on the
display for 15 minutes, the brightness of the display decreases. After pressing a button, the
display returns to the initial brightness.
6)
Software (menu 7.7)
Update via interface (menu 7.7.1)
off No software update is carried out via the web interface
on Software updates can be carried out via the web interface
UPDATE (menu 7.7.2)
If a software package has been transferred to the device, the package can be installed (again) here.
7.11 Commissioning (menu 8)
The commissioning wizard queries all relevant parameters.
Language (8.2)Select
Date (8.3) Set
Time (8.4) Set
Usys L-L (8.5) System voltage
Frequency (8.6) 50 or 60 Hz
INGR nom (8.7)
RNGR nom (8.8)
CT primary (8.9)
CT secondary (8.10)
CT connection (8.11) 50 mA or 5 A
Field calibration (8.12) Start or do not start

Table of Contents

Other manuals for Bender NGRM700

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Bender NGRM700 and is the answer not in the manual?

Bender NGRM700 Specifications

General IconGeneral
BrandBender
ModelNGRM700
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals