Technical data
71
NGRM7xx_D00292_07_M_XXEN/02.2022
Monitoring R
NGR
Measuring input R
S
...................................................................................................................................................< 33 V RMS
Measuring range NGR (with R
S
= 20 kΩ) active........................................................................................................0…10 kΩ
Measurement uncertainty for T = 0…+40 °C................................................................................................±20 Ω
Measurement uncertainty for T = –40…+70 °C........................................................................................... ±40 Ω
Measuring range NGR (with R
S
= 100 kΩ) active......................................................................................................0…10 kΩ
Measurement uncertainty for T = 0…+40 °C................................................................................................±30 Ω
Measurement uncertainty for T = –40…+70 °C........................................................................................... ±80 Ω
HRG
Setting range R
NGR nom
............................................................................................................................. 15 Ω…5 kΩ
Response value <R
NGR nom
.........................................................................................................10…90 % R
NGR nom
Response value >R
NGR nom
.....................................................................................................110…200 % R
NGR nom
LRG
Setting range R
NGR nom
............................................................................................................................. 0.1…200 Ω
Response value >R
NGR nom
..................................................................................................................... 200…500 Ω
Response delay, NGR-fault relay ..............................................................................................................................7 s (±2.5 s)
Response delay, trip relay..............................................................................................................................................0…48 h
Monitoring I
NGR
Measuring circuit 5 A
Nominal measuring current I
n
.............................................................................. DC / 50/60 Hz / 50…3200 Hz 5 A
Maximum continuous current ..............................................................................................................................2 x I
n
Overload capacity.................................................................................................................................10 x I
n
for 0.03 s
Measurement accuracy................................................................................................................................ ±2 % of I
n
Load..................................................................................................................................................................... 10 mΩ
Measuring circuit 50 mA
Nominal measuring current I
n
.........................................................................DC / 50/60 Hz / 50…3200 Hz 50 mA
Maximum continuous current ..............................................................................................................................2 x I
n
Overload capacity......................................................................................................................................10 x I
n
for 2 s
Measurement accuracy................................................................................................................................ ±2 % of I
n
Load.........................................................................................................................................................................68 Ω
Measuring circuits 5 A and 50 mA
Response value I
NGR
......................................................................................................................10…90 % I
NGR nom
Response delay, ground-fault relay.............................................................................................. ≤ 40 ms (±10 ms)
Response delay, trip relay (configurable)......................................................................................100 ms…48 h, ∞

Table of Contents

Other manuals for Bender NGRM700

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Bender NGRM700 and is the answer not in the manual?

Bender NGRM700 Specifications

General IconGeneral
BrandBender
ModelNGRM700
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals