5 - PARAMETER GROUPS
Number Parameter Setting Range Units Default Page
P41 Auto Fault Reset Time Off, 1 – 900 Seconds Off 104
P42 Auto Reset Limit Off, 1 – 10 Off 104
P43 Controlled Fault Stop Enable Off, On On 105
P44
Independent Starting/Running
Overload
Off, On Off 106
P45 Motor Starting Overload Class Off, 1 – 40 10 107
P46 Motor Overload Hot/Cold Ratio 0 – 99 % 60 108
P47 Motor Overload Cooling Time 1.0 – 999.9 Minutes 30.0 109
P48 DI 1 Configuration
OFF: Off
StOP: Stop
FH: Fault High
FL: Fault Low
Fr: Fault Reset
diSc: Disconnect
InLn: Inline Cnfrm
byP: Bypass Cnfrm
EoLr: E OL Reset
L-r: Local/Remote
hdIS: Heat Disable
hEn: Heat Enable
rSEL: Ramp Select
SS F: Slow Speed
Forward
SS R: Slow Speed Reverse
bdIS: DC Brake Disable
bEn: DC Brake Enable
runE Run Enable
rund Run Disable
Stop
110
P49 DI 2 Configuration
Off
P50 DI 3 Configuration
Off
P51 Digital Fault Input Trip Time 0.1 – 90.0 Seconds 0.1 111
P52 R1 Configuration
OFF: Off
FLFS: Fault (fail safe)
FLnF: Fault (non fail safe)
run: Running
utS: UTS
AL: Alarm
rdyr: Ready
LOC: Locked Out
OC: Over Current
UC: Under Current
OLA: OL Alarm
ShFS: Shunt Trip
(fail safe)
ShnF: Shunt Trip
(non fail safe)
gfLt: Ground Fault
ES: Energy Saver
HEAt: Heating
SSPd: Slow Speed
SS F: Slow Speed
Forward
SS r: Slow Speed Reverse
dcb: DC Braking
FAn: Cooling Fan
FLFS
112
P53 R2 Configuration
Off
P54 R3 Configuration
Off
P55 Analog Input Trip Type
Off: Disabled
Lo: Low Level
Hi: High Level
Off 113
P56 Analog Input Trip Level 0 – 100 % 50 114
P57 Analog Input Trip Delay Time 0.1 – 90.0 Seconds 0.1 114
P58 Analog Input Span 1 – 100 % 100 115
P59 Analog Input Offset 0 – 99 % 0 116