EasyManua.ls Logo

Berthold Duo Xpert - PV Alarm Settings

Berthold Duo Xpert
233 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7 Main Menu Device Setup LB 470 Level
144
56925BA2 Rev. 03, 11/2017
PV Alarm Settings
Device settings | Setup | Alarms | PV alarm settings
You can set the values for the level alarms (max. and min.) and the hysteresis of
these in the submenu PV Alarm Settings.
When exceeding or falling below the switching point, an event message appears
in the status display. If a digital output "min. level Alarm" or "max. level Alarm" is
assigned under the function (Fig. 126, item 6), the relay switches.
Hysteresis is defined as the tolerance range of the alarm trigger which occurs at a
predefined threshold of the process range.
1
2
3
4
Selection box “PV low
Selection box “PV high
Input box “Switch point Low
Input box “Hysteresis Low”
5
6
7
8
Input box “Switch point High”
Input box “Hysteresis Low”
Event message “Failure
Event message “Out of specifica-
tion”
Fig.
127 PV Alarm Settings
Example: Tolerance range = 5%, Process range = 20% and 85%
In the event of a rising process range, the max. alarm is triggered when a process
range of 85% is exceeded. When the process range falls again, then the alarm does
not switch off again until the process range falls below 85% - 5% = 80%.
In the event of a falling process range, the min. alarm is triggered when a process
range falls below 20%. When the process range rises again, then the alarm does
not switch off again until the process range rises above 20% + 5% = 25%.

Table of Contents