Probus DP V1 Agile 06/201016
Baud Rate Setting / Line Length
8 Baud Rate Setting / Line Length
The baud rate is not set explicitly. The Profibus component supports the Auto_Baud
independently determines the baud rate set on the bus.
The maximum line length recommended by the PNO correlates to the baud rate.
Profibus-DP Interface
Baud Rate/kBaud Max. Line Length/m
1200
1200
1200
1200
1000
500 400
1500 200
3000 100
6000 100
12000 100
9 Setting the Station Address
391 Profibus Node-ID
A maximum of 125 slave frequency inverters can be operated on the Profibus-
DP. Each frequency inverter
is assigned a node ID for its unambiguous ide
ntification; this ID may only exist once in the system. The
setting of the node ID is carried out via Parameter Profibus Node-ID 391.
Parameter Setting
391 Profibus Node-ID -1 126 -1
Note:
391 = -1 means Profibus function switched off.