Probus DP V1 Agile 06/201060
Annex
18.2 Warning Messages Application
When the highest bit in the Warning messages is set, a “Warning Message Application” is present.
The Application warning messages are given via parameter Application Warnings 274, bit-coded
according to the following scheme.
Parameter
Application Warnings 273 shows
the warnings in clear text on the operator panel and
the PC software tool VPlus.
Use Parameter
274 to access the Application warning codes via Profibus.
Warning Messages
Bit-No. Warning
Code
Description
0 0x0001 BELT
1 0x0002 (reserved)
2 0x0004 (reserved)
3 0x0008 (reserved)
4 0x0010 (reserved)
5 0x0020 (reserved)
6 0x0040 SERVICE
7 0x0080 User 1
8 0x0100 User 2
9 0x0200 (reserved)
10 0x0400 (reserved)
11 0x0800 (reserved)
12 0x1000 (reserved)
13 0x2000 (reserved)
14 0x4000 (reserved)
15 0x8000 (reserved)
Note: The meaning of the individual warnings are described in detail in the operating
instructions.
18.3 Error Messages
The error
code that is stored after a fault occurs is made up of the fault group FXX (high Byte,
hexadecimal) followed by the code number XX (low Byte, hexadecimal).
Communication Fault
Code Meaning
F20 62 Profibus OFF (communication connection to DP Master lost)*
F26 02 Communication watchdog CM-PDPV1 / inverter controller
*
This message only appears whenever
393 = 1 – Error.
The Actual error message can also be read out by parameter access via parameter
260.
Parameter
Actual Error 259 shows the actual error in clear text on the operator panel and the PC
software tool VPlus.
In addition to the fault messages stated, there are further fault messages used for internal purposes
only and which are not listed here. If you receive any fault mes
sages which are not listed, please
contact us by phone.