EasyManua.ls Logo

BONFIGLIOLI Vectron Agile Series User Manual

BONFIGLIOLI Vectron Agile Series
64 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #27 background imageLoading...
Page #27 background image
Probus DP V1 Agile 2706/2010
Handling of the Objects
16.1.1 Request Identification
Structure of the request identification AK (output data set, Master Slave)
Request
Identification AK
Data type Function
0 - no request
1 int/uint , long read parameter value
2 int/uint write parameter value int/uint
3
long
write parameter value long
6
int/uint , long Array
read parameter value Array
7
int/uint Array
write parameter value int/uint Array
8 long Array write parameter value long Array
Array:
Applies to data set change-over capable parameters; the required data must be specified in
data set/INDEX. Otherwise, data set/INDEX = 0.
16.1.2 Response Identification
Structure of the reply identification AK (input data set, Slave Master)
Reply
Identification AK
Data type Function
0 - no request
1 int/uint transmit parameter value int/uint
2 long transmit parameter value long
4
int/uint Array
transmit parameter value int/uint Array
5 long Array transmit parameter value long Array
7
-
request cannot be implemented
8 - no control sovereignty for PKW interface
If the reply identification = 7 (request cannot be implemented), an error code is inserted in PWE low
(Byte 6/7).
If the reply identification = 8 (no control sovereignty), the master has no writing right to the slave.
16.1.3 Fault Messages
Coding of the fault messages in the reply data set PWE-Low/Low-Byte in Byte 7 (Slave Master):
Fault No. (dec.)
acc. to
PROFIDRIVE
Meaning
0
Inadmissible parameter number PNU
1
Parameter value cannot be altered
2 Lower or upper parameter value limit exceeded
3 Faulty data set
4 No data set change-over capable parameter
5 Wrong data type
18
Other fault
20
Systembus not responding
Extension
Meaning
101
Parameter cannot be read
103
Fault occurred in reading the EEPROM
104
Fault occurred in writing the EPROM
105
Check sum fault in EEPROM occurred
106
Parameter may not be written in operation
107 Values of the data sets differ
108
Unknown request
Handling of the Objects
Note:
The fault number „20“ can be caused by different reasons.
If you do not use the Systembus: Check, that the Low-Byte is “0” (Zero). Values big
ger than zero will
try to communicate with a Systembus connected device instead of the Profibus device.
If you use Systembus (in example via an EM-
SYS module), the requested device doesn’t respond.
Check, that the requested device is supplied with power and that the Systembus Node ID in the Index
Low Byte and the parameterization of the requested device match.
16.1.4 Parameters, Data Set Selection and Cyclic Writing
Parameters to be set can be taken from the parameter list referring to the configura
tion of the
standard operating instructions. In the parameter list, state whether a parameter is data set change-
over capable (data set/INDEX = 1 to 4) or only exists once (data set/INDEX = 0).
The parameter list also provides information on the display format of a parameter and its type
(int/uint/long). String parameters cannot be transmitted due to the possible number of bytes.
The values transmitted are always integer values. For values with decimal places, the decimal point is
not transmitted.
The word IND passes on the required data set of the parameter. In the present appli
cation, the data
set number 0 is assigned to existing parameters; a selection from multiple (data set change-
over
capable) existing parameters is carried out by inserting a number from 1 to 4.
The actual parameter value is transmitted i
n the PWE area; as a 16 Bit value (int/uint) it occupies
PWEl, as a 32 Bit value (long) PWE high and PWE low, with the high word located in PWE high.
If parameters with four data values are set via data set = 0, all four data sets are set to the same
tr
ansmitted value. A read access with data set = 0 to such parameters is only successful if all four
data sets are set to the same value. If this is not the case an error is reported.
Caution! The values are entered automati
cally into the EEPROM on the controller.
If values are to be written cyclically with a high repetition rate, there must
be no entry into the EEPROM, as it only has a limited number of
admissi
ble writing cycles (about 1 million cycles). If the number of
admissible writing cycles is exceeded, the EEPROM is destroyed.
To avoid this, cyclically written data should be transmitted into the RAM (only
without a writing cycle
onto the EEPROM). Then the data are not stored secure against zero voltage and must be w
ritten
again after a Power off/on.
This mechanism is activated by the target data set being increased by five in the spe
cification of the
data set (IND).
Entry only into the RAM:
EEPROM RAM
Entry into data set 0 Data set (IND) = 5
Entry into data set 1 Data set (IND) = 6
Entry into data set 2 Data set (IND) = 7
Entry into data set 3 Data set (IND) = 8
Entry into data set 4 Data set (IND) = 9
Writing access to data set change-over capable parame
ters is to be considered as a further special
point. If the values of a data set change-
over capable parameter are to be set to the same value in all
data sets, the parameter can be written via the data set (IND) 0.

Table of Contents

Question and Answer IconNeed help?

Do you have a question about the BONFIGLIOLI Vectron Agile Series and is the answer not in the manual?

BONFIGLIOLI Vectron Agile Series Specifications

General IconGeneral
Fieldbus CommunicationCANopen, Modbus RTU
ProtectionOvervoltage; Undervoltage
Control InterfaceDigital Inputs, Analog Inputs
Operating Temperature Range-10°C to +50°C
Cooling MethodLiquid cooling
Enclosure RatingIP20
DimensionsVaries by model
WeightVaries depending on the model
Storage Temperature Range-20°C to 70°C

Summary

General Information on the Documentation

Instruction Manuals

Describes the various manuals available for the Agile device series for different user needs.

General Safety Instructions and Information on Use

General Information

Provides general warnings regarding high voltage, hot surfaces, and the need for qualified personnel.

Purpose of the Frequency Inverters

Explains the intended industrial applications of frequency inverters and compliance with directives.

Transport and Storage

Outlines proper procedures for transporting and storing the frequency inverters to maintain their condition.

Handling and Installation

Covers essential precautions for handling, installation, and electrical installation to prevent damage and ensure safety.

Electrical Installation

Details safety rules and compliance requirements for electrical installation work on the inverters.

Information on Use

Details operational guidelines, restart procedures, and checks before commissioning.

Using external products

Advises on the responsibility for compatibility when using external products with the inverter.

Maintenance and Service

Stresses the importance of authorized personnel for maintenance and service to prevent injury or damage.

Disposal

States that disposal must be carried out according to local and country-specific regulations.

Communication Options

VPlus PC-Software

Explains how to connect a PC via USB adapter to the X21 interface for parameterization and monitoring.

Installation of an optional Communication Module

Assembly

Provides step-by-step instructions for assembling the communication module onto the frequency inverter.

Disassembly

Details the procedure for safely removing the communication module from the frequency inverter.

Connection

Commissioning via the Operator Panel

Menu for setting up the Communication

Guides users on how to configure communication interfaces and parameters using the operator panel menus.

Select the Protocol

Describes how to select the communication protocol (e.g., Profibus) within the setup menu.

Set the Communication Parameters

Explains how to set specific communication parameters like Node Number using the operator panel.

Profibus

Baud Rate Setting / Line Length

Setting the Station Address

LED Indicators

Status Parameters

Error Behavior

Setting PPO Type

Configuration Process on the DP Master

Illustrates the configuration steps using a Siemens STEP7 hardware configurator example.

Commands SYNC / FREEZE

Available Objects / Scanning Times

Handling of the Objects

Parameter Access via Communication Channel PKW

Details the structure and usage of the PKW area for parameter access and identification.

Parameter Access via the DP-V1 Channel

Describes an alternative method for parameter access using the Profibus V1 channel.

Process Data Channel

Describes the handling of Process Data Objects (PZDs) for data exchange.

Frequency Conversion PDP Word to/from Inverter Internal Notation

Explains the function for converting frequency values between Profibus and internal notations.

Actual Value Display of Profibus Data

Explains how Profibus data is displayed in a processed form via PC software.

Parameter List

Actual Values

Lists actual values of frequency inverter parameters, their units, display range, and relevant chapters.

Parameters

Lists various parameters related to Profibus communication, control, and stopping behavior.

Annex

Warning Messages

Details warning codes and their descriptions activated by the Profibus-DP module.

Warning Messages Application

Lists application-specific warning codes and their descriptions.

Error Messages

Explains the structure of error codes and lists common communication errors.

Related product manuals