EasyManuals Logo

BONFIGLIOLI Vectron Agile Series User Manual

BONFIGLIOLI Vectron Agile Series
64 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #27 background imageLoading...
Page #27 background image
Probus DP V1 Agile 2706/2010
Handling of the Objects
16.1.1 Request Identification
Structure of the request identification AK (output data set, Master Slave)
Request
Identification AK
Data type Function
0 - no request
1 int/uint , long read parameter value
2 int/uint write parameter value int/uint
3
long
write parameter value long
6
int/uint , long Array
read parameter value Array
7
int/uint Array
write parameter value int/uint Array
8 long Array write parameter value long Array
Array:
Applies to data set change-over capable parameters; the required data must be specified in
data set/INDEX. Otherwise, data set/INDEX = 0.
16.1.2 Response Identification
Structure of the reply identification AK (input data set, Slave Master)
Reply
Identification AK
Data type Function
0 - no request
1 int/uint transmit parameter value int/uint
2 long transmit parameter value long
4
int/uint Array
transmit parameter value int/uint Array
5 long Array transmit parameter value long Array
7
-
request cannot be implemented
8 - no control sovereignty for PKW interface
If the reply identification = 7 (request cannot be implemented), an error code is inserted in PWE low
(Byte 6/7).
If the reply identification = 8 (no control sovereignty), the master has no writing right to the slave.
16.1.3 Fault Messages
Coding of the fault messages in the reply data set PWE-Low/Low-Byte in Byte 7 (Slave Master):
Fault No. (dec.)
acc. to
PROFIDRIVE
Meaning
0
Inadmissible parameter number PNU
1
Parameter value cannot be altered
2 Lower or upper parameter value limit exceeded
3 Faulty data set
4 No data set change-over capable parameter
5 Wrong data type
18
Other fault
20
Systembus not responding
Extension
Meaning
101
Parameter cannot be read
103
Fault occurred in reading the EEPROM
104
Fault occurred in writing the EPROM
105
Check sum fault in EEPROM occurred
106
Parameter may not be written in operation
107 Values of the data sets differ
108
Unknown request
Handling of the Objects
Note:
The fault number „20“ can be caused by different reasons.
If you do not use the Systembus: Check, that the Low-Byte is “0” (Zero). Values big
ger than zero will
try to communicate with a Systembus connected device instead of the Profibus device.
If you use Systembus (in example via an EM-
SYS module), the requested device doesn’t respond.
Check, that the requested device is supplied with power and that the Systembus Node ID in the Index
Low Byte and the parameterization of the requested device match.
16.1.4 Parameters, Data Set Selection and Cyclic Writing
Parameters to be set can be taken from the parameter list referring to the configura
tion of the
standard operating instructions. In the parameter list, state whether a parameter is data set change-
over capable (data set/INDEX = 1 to 4) or only exists once (data set/INDEX = 0).
The parameter list also provides information on the display format of a parameter and its type
(int/uint/long). String parameters cannot be transmitted due to the possible number of bytes.
The values transmitted are always integer values. For values with decimal places, the decimal point is
not transmitted.
The word IND passes on the required data set of the parameter. In the present appli
cation, the data
set number 0 is assigned to existing parameters; a selection from multiple (data set change-
over
capable) existing parameters is carried out by inserting a number from 1 to 4.
The actual parameter value is transmitted i
n the PWE area; as a 16 Bit value (int/uint) it occupies
PWEl, as a 32 Bit value (long) PWE high and PWE low, with the high word located in PWE high.
If parameters with four data values are set via data set = 0, all four data sets are set to the same
tr
ansmitted value. A read access with data set = 0 to such parameters is only successful if all four
data sets are set to the same value. If this is not the case an error is reported.
Caution! The values are entered automati
cally into the EEPROM on the controller.
If values are to be written cyclically with a high repetition rate, there must
be no entry into the EEPROM, as it only has a limited number of
admissi
ble writing cycles (about 1 million cycles). If the number of
admissible writing cycles is exceeded, the EEPROM is destroyed.
To avoid this, cyclically written data should be transmitted into the RAM (only
without a writing cycle
onto the EEPROM). Then the data are not stored secure against zero voltage and must be w
ritten
again after a Power off/on.
This mechanism is activated by the target data set being increased by five in the spe
cification of the
data set (IND).
Entry only into the RAM:
EEPROM RAM
Entry into data set 0 Data set (IND) = 5
Entry into data set 1 Data set (IND) = 6
Entry into data set 2 Data set (IND) = 7
Entry into data set 3 Data set (IND) = 8
Entry into data set 4 Data set (IND) = 9
Writing access to data set change-over capable parame
ters is to be considered as a further special
point. If the values of a data set change-
over capable parameter are to be set to the same value in all
data sets, the parameter can be written via the data set (IND) 0.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the BONFIGLIOLI Vectron Agile Series and is the answer not in the manual?

BONFIGLIOLI Vectron Agile Series Specifications

General IconGeneral
BrandBONFIGLIOLI
ModelVectron Agile Series
CategoryDC Drives
LanguageEnglish

Related product manuals