PRAESENSA Event messages | en 141
Bosch Security Systems B.V. Configuration manual 2020-09 | V1.20 | PRAESENSA 1.20
Event: User logged in
Group: General
Occurrence: Logs the user ID which has logged in to the system.
Originator: Device on which the login occurred or IP‑address of the client from which the
login has occurred including the user‑ID which has logged in.
Event: User login attempt failed
Group: General
Occurrence: Logs when a login attempt has failed. During a lock out due too many login
attempts this event is not logged.
Originator: Device on which the login attempt occurred or IP‑address of the client from
which the login attempt occurred including the user‑ID that was used in the attempt.
Event: User logged out
Group: General
Occurrence: Logs the user‑ID which has logged out from the system.
Originator: Device on which the log off occurred or IP‑address of the client that logged off
including the user‑ID which has logged out.
General device fault events
Event: Mains supply fault: external
Group: Fault
Occurrence: Can occur on all devices when they receive a trigger on a control input
configured as backup power mode.
Originator: Device which triggered the backup power mode.
Resolve: When the backup power mode is switched off or when the device disconnects.
Recommended action: Check powering device(s) and lines/connections.
Extra information: Aggregate to main power fault.
Event: Fan rotation fault: fan 1/2
Group: Fault
Occurrence: Logs that fan 1/2 of a device in the system has a fault.
Originator: Device that has the fan 1/2 fault.
Resolve: When the Fan 1 fault is not present anymore.
Recommended action:
Check the correct functionality of the device fan. Or
remove device and replace/repair fan (circuit).
Event: Ground fault
Group: Fault
Occurrence: Logs the ground short fault of a device in the PRAESENSA system.
Originator: Device that has the ground short fault.
Resolve: When the Short Fault is not present anymore.
Recommended action: Check and remove the ground short of the reported device.